How to troubleshoot the failure of the material aging test chiller?
Regular maintenance work for the material aging test chiller, and troubleshooting is also very important.
1. Exhaust at double high pressure, heat dissipation may be problematic.
When it is detected that the high and low pressure of the system are higher than normal, it is usually because there is air in the system or excessive refrigerant is added. At this time, it is necessary to re-evacuate and add an appropriate amount of refrigerant to solve the problem. However, there is another situation, that is, poor heat dissipation, especially when the ambient temperature is relatively high, which often leads to worse heat dissipation. The cause of this failure is generally that the heat sink is blocked, dirty, and the speed of the heat dissipation fan is not enough.
2. Refrigerant with low pressure loss, otherwise the system will be blocked.
When the high and low pressures are both low, there are two possibilities:
(1) If the system is blocked, the blocked part will produce throttling, and there will be a significant temperature difference in the throttling part, and the problem can be found by feeling it with your hands.
(2) The leakage of refrigerant leads to insufficient refrigerant. This situation is more common. At this time, the material aging test cooler detector must be used to find out the leaking location and perform replacement.
3. Low pressure, high pressure, low pressure, replace the compressor.
When the material aging test cooler pressure gauge detects that the low pressure is higher than normal, and the high pressure is lower than normal, at this time, it is recommended that the chiller refrigeration cannot achieve the effect of the normal material aging test refrigeratore. The reason is likely to be the wear and tear in the material aging test refrigeratore pump, resulting in a drop in power. At this time, it is often necessary to replace the compressor to solve the problem.
4. There is water vapor in the meter shake system, so it must be changed when it is timed out.
When the material aging test cooling machine system is working, if the pressure gauge needle keeps shaking, it means that there is moisture in the system. To solve this problem, it is generally necessary to re-evacuate, and the pumping time must be no less than 15 minutes. If necessary, the drying bottle needs to be replaced to drain the water in the system.
Raccomandazioni correlate
-
Guida alla scelta del circolatore di raffreddamento e riscaldamento per laboratorio
2019Quando si acquistano apparecchiature di raffreddamento e riscaldamento per laboratorio, il punto chiave è soddisfare i requisiti di produzione e accelerare la produzione. Pertanto, è necessario comprendere le caratteristiche dell'apparecchiatura e le soluzioni tecniche ...
Visualizza dettagli -
The importance of temperature cycle control heating and cooling in the production of API
2353China has become the world's largest supply market for APIs. Most of the APIs and intermediates required by foreign manufacturers are purchased in my country. The drug outsourcing process of most of its preparation products, the production process...
Visualizza dettagli -
Piccolo accoppiamento per affrontare l'intasamento da ghiaccio dei refrigeratori a circolazione di liquido ad alta e bassa temperatura
1618Nel funzionamento dei refrigeratori a circolazione di liquido ad alta e bassa temperatura, il blocco del ghiaccio è un guasto relativamente comune. Sulla base dell'esperienza dei produttori del settore, abbiamo raccolto alcuni suggerimenti per affrontare il problema dell'intasamento da ghiaccio. Nelle tubazioni...
Visualizza dettagli -
Trouble shooting method for refrigeration device of air-cooled chiller chemical reaction kettle
1867If air enters into the air-cooled chiller refrigeration unit system of the chemical reaction kettle, the impact will be many. Enter the air circulation system first, the pressure will rise, the heat dissipation effect of the condenser will also be...
Visualizza dettagli
工業冷水機製造商 LNEYA Taiwan