1. Communication Failure:
Computer controller controls various modules by telecommunication lines and total interface board, so the main cause of communication failure is poor contact or break of communication lines, especially the interface oxidation and damp of the interface. Also, the failure of unit electronic board or total interface board, incorrect choice of address dial code switch and power failure can cause the communication failure.
2. Low Voltage Failure:
The low suction pressure of the compressor results in low pressure protection relay action. The suction pressure of the compressor reflects the evaporation pressure, whose the normal value should be 0.4~ 0.6mpa, and the protection value is set to 0.2mpa. Low suction pressure causes low return air volume and insufficient cooling capacity, resulting in waste of electrical energy and the heat dissipation of the motor of gas cooled compressor which is easy to damage the motor.
3. High Voltage Failure:
High exhaust pressure of compressor results in high voltage protection relay action. The compressor exhaust pressure reflects condensation pressure whose normal value should be 1.4~ 1.6mpa, and the protection value is set to 2.0mpa. If the pressure is too high for a long time, it will cause too large of the current of compressor, which is easy to burn the motor and damage the compressor exhaust valve disc.
関連推奨品
-
The Installation Requirement of the Industrial Chiller
1945(1) The chiller power supply adopts three-phase four-wire, power supply line (R, S, T) connected with power supply fire line, (N) zero line, (G) ground line.
詳細を見る -
工場ボイラーの操作に関する誤解
1806ボイラーは工場ではごく一般的な設備だ。LNEYAシャオビアンは、多くの人がボイラーについて誤解していると皆に言う。誤解1 蒸気圧は高ければ高いほど良い。ボイラーの蒸気圧の選択は主に...
詳細を見る -
半導体チップ用高温・低温試験機の必要性
1904チップ産業の急速な発展は誰の目にも明らかです。LNEYA半導体チップ高温・低温試験機もまた、チップ産業の発展とともに絶えず発展してきました。その数、数万台。
詳細を見る -
Detailed Operating Instructions of Industrial Chiller
2545The installation procedures of water chiller include: 1. During installation, please check whether the machine is damaged and select a suitable place for installation and future maintenance. The site for installing the unit must be the floor o...
詳細を見る
工業冷水機製造商 LNEYA Taiwan