Three Common Failures Of Air Cooled Screw Chiller
Three Common Failures Of Air Cooled Screw Chiller
1. Communication Failure:
Computer controller controls various modules by telecommunication lines and total interface board, so the main cause of communication failure is poor contact or break of communication lines, especially the interface oxidation and damp of the interface. Also, the failure of unit electronic board or total interface board, incorrect choice of address dial code switch and power failure can cause the communication failure.
2. Low Voltage Failure:
The low suction pressure of the compressor results in low pressure protection relay action. The suction pressure of the compressor reflects the evaporation pressure, whose the normal value should be 0.4~ 0.6mpa, and the protection value is set to 0.2mpa. Low suction pressure causes low return air volume and insufficient cooling capacity, resulting in waste of electrical energy and the heat dissipation of the motor of gas cooled compressor which is easy to damage the motor.
3. High Voltage Failure:
High exhaust pressure of compressor results in high voltage protection relay action. The compressor exhaust pressure reflects condensation pressure whose normal value should be 1.4~ 1.6mpa, and the protection value is set to 2.0mpa. If the pressure is too high for a long time, it will cause too large of the current of compressor, which is easy to burn the motor and damage the compressor exhaust valve disc.
Recommandations connexes
-
Troubleshoot fan failures in the cooling system of the engine powertrain
1997The fan is generally installed at the upper end of the cooling system of the engine powertrain, and some customers choose to install it on the side according to regulations. For screw chillers that use fans to dissipate heat, they are called air-c...
Voir les détails -
LNEYA high and low temperature heating refrigerator maintenance instructions
2211High and low temperature heating refrigerators use circulating water to replace circulating water regularly every month. If heat transfer oil is used, heat transfer oil should be replaced periodically every six months to one year. When the high an...
Voir les détails -
About the size and installation height of refrigeration heating temperature control system equipment
1664Whether it is biopharmaceutical, traditional Chinese medicine or chemical pharmacy, pharmaceutical companies are all related to chemistry, because the extraction and synthesis of pharmaceutical ingredients are all in the form of chemical products...
Voir les détails -
Installation Requirements For Ethylene Glycol Cryo Chillers
1907After the purchase of ethylene glycol cryo chillers with professional manufacturers Wuxi Guanya, installation requirements will be sent to the hands of users with the equipment. So, what needs to be paid attention to during the installation of eth...
Voir les détails
工業冷水機製造商 LNEYA Taiwan