航空宇宙機器部品極低温試験フリーザー冷凍トラブルシューティング説明書
Cooling water inlet temperature is too low
Ultra-low temperature freezer for ultra-low temperature testing of aerospace equipment components As the temperature of the cooling water decreases, the compressor discharge pressure, exhaust temperature, and filter outlet temperature are reduced. The temperature remains the same, because the cooling water temperature has not dropped to the extent that it will affect the cooling effect. If the temperature of the cooling water drops to a certain level, the condensing pressure will also decrease, so that the pressure difference between the two sides of the thermal expansion valve will decrease, the flow capacity of the thermal expansion valve will also decrease, and the refrigerant will also decrease, so the cooling effect will be reduced. .
Cooling water inlet temperature is too high
If the temperature of the cooling water inlet is too high, the refrigerant will be too cold, the condensation temperature will be too high, the condensing pressure will be too high, the compressor pressure ratio will increase, the shaft power will increase, and the gas transmission coefficient will decrease, thus reducing the cooling capacity of the system. Therefore, the cooling effect of the ultra-low temperature freezer for ultra-low temperature testing of aerospace equipment components will be reduced and the temperature will rise.
Circulating pump does not turn
When the ultra-low temperature freezer for ultra-low temperature testing of aerospace equipment components is commissioned and operated, the system circulating water pump should be opened first. When the circulating water pump does not rotate, the temperature of the cooling water outlet and the temperature of the refrigerant outlet of the condenser rise more obviously. Due to the sharp decrease of the cooling effect of the condenser, the suction temperature and the exhaust temperature of the compressor also rise rapidly, and the condensation temperature The rise also causes the evaporation temperature to rise, but the extent of the rise in the evaporation temperature is not as large as the increase in the condensation temperature, so the refrigeration efficiency is lowered and the temperature is rapidly increased.
The fan does not turn
There are two reasons why the fan does not turn. First, the electrical fault, the control circuit is not connected; the second is the mechanical failure of the fan shaft.
When the ultra-low temperature freezer fan of the aerospace equipment component ultra-low temperature test does not turn, the temperature will rise, and the suction pressure and exhaust pressure of the compressor will decrease to some extent. After the fan is not turned, the heat exchange efficiency of the inner heat exchange coil is lowered, and the temperature rises when the heat load is constant.
The refrigerant in the heat exchange coil is insufficient in heat exchange, and its temperature is lowered relative to the original temperature, that is, the evaporation temperature becomes smaller, and the refrigeration coefficient of the system is lowered. The evaporator outlet temperature felt by the thermal expansion valve is also lowered, so that the opening of the thermal expansion valve becomes smaller and the refrigerant is correspondingly reduced, so the suction and exhaust pressures are all reduced. The overall effect of the reduction in refrigerant flow and the reduction in the refrigeration coefficient is to reduce the cooling capacity of the system.
Filter blocked
The filter is blocked and the system is dirty. Under normal circumstances, dirty plugging often occurs at the filter. This is because the filter screen of the ultra-low temperature freezer filter for ultra-low temperature testing of aerospace equipment components blocks the passage section and filters out dirt and metal chips and other debris for a long time. And it was blocked.
These failures of ultra-low temperature freezer for ultra-low temperature testing of aerospace equipment components are still not too difficult. If we encounter unknown difficulties, we do not need our operators to challenge them, or they are solved by specialized technicians.
関連推奨品
-
原子炉温度制御システムの設置方法と使用方法は?
2073原子炉温度制御システムを購入後、多くのユーザーが設置工事に取り掛かろうとしています。設置時に注意すべきことは何ですか?反応器温度制御システムの反応釜を設置する時、必要なことは...
詳細を見る -
塩水噴霧環境チャンバーの一般的な不具合
1993塩水噴霧環境槽の一般的な故障に対処する際、企業ユーザーはしばしば途方に暮れる。そのため、塩水噴霧環境室のメーカーである無錫LNEYA社は、塩水噴霧環境室に関連する一般的な故障を特別に再編成し、塩水噴霧環境室における一般的な故障を解決するための方法を提供する。
詳細を見る -
Disadvantages and advantages of general heat transfer oil heating circulation system
2127熱伝導オイル加熱サーキュレータは、直接加熱medium.Its利点に熱エネルギーに作用するように完全に閉じたループ構造を採用しています:(1)熱伝達表面の連続的な更新のために、熱損失は小さいです; (2...
詳細を見る -
チップバーンイン試験におけるVCSELとは?温度による影響は?
2881VCSELの正式名称はVertical-cavity Surface-emitting Laserで、中国名は垂直共振器面発光レーザー。半導体レーザーの一種です。半導体レーザーは、半導体製造技術を用いて製造されるレーザーです。
詳細を見る
工業冷水機製造商 LNEYA Taiwan