A que devo prestar atenção ao substituir um compressor de chiller arrefecido a água?
Once the compressor of the water-cooled
chiller fails, the compressor needs to be replaced in time, but the replacement
of the compressor is not as simple as imagined.
Before the water-cooled chiller compressor
is replaced, the reasons for the damage to the original compressor must be
checked, and the defective parts must be replaced. Because the damage of other
parts of the water-cooled chiller will directly cause damage to the compressor.
After removing the original damaged compressor, the system must be purged with
nitrogen before the new compressor system can be connected.

During the welding operation of the
water-cooled chiller, in order not to form an oxide film on the inner wall of
the copper pipe, it is recommended to pass in nitrogen gas, and the time to
pass the nitrogen gas should be sufficient. It is forbidden to use the
compressor as a vacuum pump to empty the air in the pipeline of the external
machine when replacing the compressor or other parts, otherwise the compressor
will be burned, and a vacuum pump must be used to vacuum. When replacing, you
must add refrigerating oil that meets the nature of the compressor, and the
amount of refrigerating oil should be appropriate. Generally speaking, the new
original compressor has refrigerating oil.
When replacing the water-cooled chiller
compressor, the filter drier must be replaced in time. Because the desiccant in
the desiccant filter has been saturated and has lost the water filtering
function, clean the refrigerating oil in the original system. Because the new
pump has been injected with sufficient mass-produced refrigerated lubricating
oil, refrigerating oils of different brands cannot be mixed, otherwise it will
Deterioration causes poor lubrication, causing the compressor to pull cylinders,
turn yellow, and burn.
When replacing the compressor of a
water-cooled chiller, attention should be paid to prevent excessive
refrigerating oil in the system, otherwise the heat exchange effect of the
system will be reduced, which will increase the pressure of the system and
damage the system and the compressor. Do not fill the refrigerant too fast,
otherwise it will cause liquid shock, which will cause the valve plate to break
and cause the compressor to lose pressure.
After the compressor of the water-cooled
chiller is installed, check that the compressor is working normally, such as:
suction pressure/temperature, discharge pressure/temperature, oil pressure
differential pressure and other system parameters. If the parameter exceeds the
normal value, the reason for the abnormal system parameter must be clarified.
Recomendações relacionadas
-
Multi-stage refrigeration system centrifugal compressor repair instructions
2548After the centrifugal compressor of the cascade refrigeration system is disassembled, the dimensions of each journal (cooperating with the impeller, bearing, coupling, etc.) are measured with an outer diameter micrometer to calculate the roundness...
Ver detalhes -
Operation method of reaction kettle for circulating heating device
2049The laboratory single-layer glass reactor equipped with the circulating heating device can place a flask containing the reaction solvent on the inner layer for stirring reaction, and the interlayer can realize constant temperature heating and cons...
Ver detalhes -
Efeito da Temperatura nas Reacções de Síntese Química Orgânica
2421A síntese orgânica é um fenómeno químico comum na química. A temperatura tem uma influência importante durante todo o processo de síntese. À medida que a temperatura aumenta, a reação de absorção de calor acelera, resultando numa alteração significativa...
Ver detalhes -
Ganhou o prémio "Excelente fornecedor de equipamento de controlo da temperatura de reactores em 2021"
4931LNEYA was awarded the "2021 Excellent Supplier of Reactor Technology" by Corning, a Fortune 500 company in the United States. Since 2015, LNEYA has won this award for 7 consecutive years. Therefore, in the reactor manufacturing industry, we have ...
Ver detalhes
工業冷水機製造商 LNEYA Taiwan