Como resolver o problema da falha da bomba de circulação da bomba de refrigeração?
Cooling heating devices are required in many chemical pharmaceutical and laboratory applications. Then how to solve the failure of the refrigeration heating device is also concerned about how to solve it?
1. Circulating pump failure
The circulating pump fault is generally the thermal overload of the circulating pump. There are four main reasons for this fault: The first is that the outer circulating pipeline of the heat conducting oil is too long. At this time, it is necessary to shorten the outer circulation pipeline, reduce the bending of the outer circulation pipeline, and then click Equipment electrical cabinet surface thermal relay Reset button; the second is the circulation pipeline blockage, cooling and heating device which is good to tell everyone, check the circulation pipeline cleaning, install the filter, and then click the equipment electrical cabinet surface thermal relay Reset button; The third is that the circulating pump voltage is too low. It is recommended to measure whether the circulating pump voltage meets the specified range, improve the voltage environment, click the Reset button of the equipment electrical cabinet surface thermal relay; the fourth is that the thermal relay regulates the current too small. At this time, it is recommended to measure the pump current. Compare the range of thermal relays, Phillips screwdriver to properly rotate the thermal relay current, click on the equipment electrical cabinet surface thermal relay Reset button.
2. Sensor failure
A great possibility of sensor failure is wiring error. Once the fault is encountered, check the wiring situation. At this time, you should pay attention to two situations, one is sensor short circuit or temperature <-160 °C, and the other is sensor open circuit or temperature > 349 ° C.
If the sensor is short-circuited or the temperature is <-160 °C, it may be the fault of the sensor itself. At this time, it is recommended to replace the sensor (there is a spare sensor in the equipment slot). If the sensor is wired incorrectly, It is recommended to check the wiring (corrected circuit diagram) correction.
If the sensor is open circuit or the temperature is >349°C, it should be the fault of the sensor itself. It is necessary to replace the sensor in time (there is a spare sensor in the equipment slot). At this time, it is necessary to pay attention to whether the temperature is too high and the temperature is too high. Check whether the temperature is exceeded. Range, if the equipment is not powered, pay attention to check the power supply of the equipment.
These two faults of the cooling heating device are still relatively simple. I believe that everyone who has seen the sharing can solve it very quickly.
Recomendações relacionadas
-
Porque é que os refrigeradores de etilenoglicol podem ser utilizados para reacções de polimerização e acoplamento
16801. Aquecimento da polimerizaçãoGeralmente, as matérias-primas da reação de polimerização são alguns solventes inflamáveis, e o aquecimento rápido pode fazer com que a temperatura local seja muito alta e causar acidentes. Cada reação de polimerização tem a sua própria reação...
Ver detalhes -
Pontos de atenção para a inspeção diária do equipamento de controlo de baixa temperatura a menos 30℃
1901O equipamento de controlo de baixas temperaturas a menos 30 graus Celsius é uma unidade de refrigeração ou também chamada unidade de refrigeração. A diferença em relação ao refrigerador é a gama de temperaturas. É um equipamento de baixa temperatura comummente utilizado na indústria...
Ver detalhes -
A solução para o alarme de falta de refrigerante no termóstato de aquecimento e arrefecimento totalmente fechado
2333O que devo fazer se o termóstato de aquecimento e arrefecimento totalmente fechado emitir um alarme por falta de líquido de refrigeração? Penso que muitos clientes irão deparar-se com este problema quando o utilizarem. De facto, é relativamente simples. Desde que se conheça o princípio ...
Ver detalhes -
Precauções para uma utilização segura do equipamento de controlo da temperatura do óleo de transferência de calor
1996Com a utilização extensiva de equipamento de controlo da temperatura do óleo térmico, a utilização segura do equipamento de controlo da temperatura do óleo térmico é uma preocupação para os utilizadores. Para os fabricantes, é muito importante partilhar as precauções de utilização dos equipamentos de controlo da temperatura dos óleos térmicos.
Ver detalhes