Explosionsgeschützter Ultratiefkühlschrank - Anweisungen für interne Leckagen
1. Sound leak detection method:
First, the refrigeration pipeline of the explosion-proof ultra-low temperature refrigerator is filled with nitrogen. Then use a stethoscope to check the interior. When you hear a leak in a certain area, mark it. Carefully pry open the metal plate at that place, check the leak point of the pipe with thick soapy water, repair by repair welding or gluing, fill the foaming agent, fill the mouth with a larger metal plate, and glue the four sides. . This method is incapable of causing micro-leakage in the refrigeration system, and is likely to cause false detection or missed detection.
2. Evaporator replacement method:
After the evaporator leak is determined, replacement repairs are performed using a finished evaporator that can be loaded into the interior of the original evaporator. Connect the new evaporator of the explosion-proof ultra-low temperature chiller to the original refrigeration line, and replace the new capillary and dryer. The disadvantage of this method is the high cost, which is powerless when encountering evaporators with special shapes or multi-door machines and leaks in the refrigeration tubes.
3. Copper tube coiling method:
This is a suitable repair method for leaks of any type of explosion-proof cryogenic refrigerator. Generally, the size of the purchased copper pipe is calculated first, and the shape and length of the copper pipe are determined according to the size of the inner casing.
4. Re-foaming maintenance method:
During the overhaul, it is necessary to open the back panel of the cabinet and dig out the original foaming material of the explosion-proof ultra-low temperature refrigerator. After exposing the evaporation tube, it is filled with nitrogen to check for leaks. Pay special attention to each connection solder joint when detecting leaks. This repair method is suitable for the case where the refrigeration system has a connector on the back, and is not suitable for the occurrence of internal leakage in the refrigeration pipe having a leak point at a deeper level. After the leak is detected, repair welding or repair with a glue pool, then re-foam and make up the back plate.
These methods of explosion-proof ultra-low temperature refrigerators can basically find out the cause of the internal leakage and solve them well.
Verwandte Empfehlungen
-
Beschreibung der Pumpenauswahl im Temperaturregler für dampfgesättigte Systeme
2020Das Temperiergerät für Dämpfungsanlagen ist eines der am häufigsten verwendeten Geräte in der pharmazeutisch-chemischen Industrie. Die Leistung des LNEYA Dampferzeuger-Temperaturreglers hängt von der Konstruktion des gesamten Systems und der Spezifikation des...
Details anzeigen -
Introduction to the structure and application of industrial refrigerators
1935Industrial refrigerators are usually called industrial refrigerator boxs, and low-temperature freezers.Temperature range: -150℃~-20℃. Industrial refrigerators can be divided into vertical and horizontal types. Most of them use imported compressors...
Details anzeigen -
483Meet Your Dream Equipment für die CBD-Destillat-Extraktion
2219Wenn Sie eine Anlage zur Destillation von CBD benötigen, müssen Sie Ihre Wahl genau prüfen, da die Geräte in ihren Eigenschaften und ihrem Design variieren können. Wenn Sie Geräte zur Herstellung von CBD-Destillaten verwenden, sollten Sie ein System von einem Hersteller wählen, der...
Details anzeigen -
How to extend the service life of heat transfer oil in dynamic temperature control system?
1884In the chemical industry, the heat transfer medium of the heat transfer oil of the dynamic temperature control system of the reactor is mainly determined by the heat transfer oil itself, the operating temperature of the heat transfer oil, the dyna...
Details anzeigen
工業冷水機製造商 LNEYA Taiwan