공냉식 냉각기 화학 반응 주전자의 냉동 장치에 대한 문제 해결 방법
If air enters into the air-cooled chiller refrigeration unit system of the chemical reaction kettle, the impact will be many. Enter the air circulation system first, the pressure will rise, the heat dissipation effect of the condenser will also be affected, and even the air-cooled cold water mechanism refrigeration unit of the chemical reactor will not operate as a result.
Therefore, we must usually develop the habit of inspections, and we should not close one eye when we find abnormalities. If we ignore small problems, they may develop into major problems.
In some cases, equipment problems are caused by long-term use. Machines, like people, always operate, and problems are inevitable. There are two types of air-cooled chiller chemical reaction kettle refrigeration unit, air-cooled and water-cooled, no matter which type, in the case of long-term use, the refrigeration system may leak. But as long as we seize the right time to deal with it, it will not cause any serious impact.
The air-cooled chiller chemical reactor refrigeration unit has entered the air. What we have to think about is how to vent it?
At this time, it depends on what kind of refrigeration system it uses. The ammonia refrigeration system is different from the Freon system.
If it is a Freon system, its bleed operation steps are as follows: close the condenser or liquid reservoir outlet valve; start the compressor; stop; let the high-pressure gas escape from the bypass hole. When the air is exhausted, the screw plug should be tightened, the exhaust valve stem should be reversely rotated, and the bypass hole should be closed.
If it is the pharmaceutical reactor refrigeration unit group of the ammonia refrigeration system, its venting step is as follows:
When using an air separator to discharge air, keep the air separator normally open and all other valves should be closed; the intake valve should be properly opened; the liquid supply valve should be opened slightly; the air discharge valve interface should be opened to the water to see the change of rising bubbles in the water. When stopping the air release, the air release valve should be closed first, in order to prevent ammonia gas from leaking out, and then close the liquid supply throttle valve and the mixed gas inlet valve. The purpose of this is to prevent the pressure in the air vent from rising, and the return valve should not be closed.
Wuxi Guanya (LNEYA) reminds: In order to avoid wasting refrigerant, the time of each deflation should not be too long, and it can be performed multiple times in a row.
관련 추천
-
고출력 산업용 냉장고 증발기 유지보수 주의사항
2181고출력 산업용 냉장고는 산업용 저온 가공에 사용됩니다. 고출력 산업용 냉장고의 증발기는 가장 중요한 구성 요소 중 하나이며 고출력 산업용 냉동기의 냉각 효과에 영향을 미치는 요소 중 하나입니다....
세부 정보 보기 -
리액터 가열 및 냉각 장치의 주요 용도는 무엇인가요?
2042원자로 가열 및 냉각 장치는 고순도 금속, 희귀 물질 정제, 실험실 환경 시뮬레이션, 마그네트론 스퍼터링, 진공 코팅 및 기타 산업에 적합합니다. 대형 극저온 펌프 장치는 냉각 효과를 제공할 수 있습니다.
세부 정보 보기 -
Heat transfer oil secondary circulation system use instructions
1949The thermal oil secondary circulation system is equipped with various instruments and equipment for temperature control. When using it, you need to pay attention to its safety knowledge and safer operation. LNEYA heat transfer oil secondary circul...
세부 정보 보기 -
온도 요구 사항을 충족하기 위한 반도체 테스트 냉각기 제어 방법
2114바이오 제약 분야에서는 효소의 활성과 제품 생산을 제어하기 위해 고정밀 온도가 필요하고, 화학 산업 분야에서는 화학 반응이 안정적으로 진행될 수 있도록 특정 온도가 필요하며, 전자...
세부 정보 보기
工業冷水機製造商 LNEYA Taiwan