심순환 냉각기의 고압 고장에 대한 솔루션
Deep-circulation chillers are process cold sources used in the production and processing of chemical and pharmaceutical intermediates, petrochemicals, machinery, medicine, electronics, new materials, aerospace, optoelectronic technology, and new energy. But how to deal with the high-pressure failure of the deep-circulation chiller?
1. The cooling water temperature is too high, and the condensing effect is not good, resulting in high pressure failure
The rated working conditions of cooling water required by deep-circulation chillers, high water temperature and poor heat dissipation, will inevitably lead to high condensing pressure. This phenomenon often occurs in high-temperature seasons. It can be solved by adding more storage tanks.
2. The cooling water flow is insufficient, and the rated water flow is not reached, resulting in a high-pressure fault
The main performance is that the pressure difference between the inlet and outlet water of the unit becomes smaller and the temperature difference becomes larger. The reason for the insufficient water flow is the lack of water in the system or the presence of air. The solution is to install an exhaust valve at the height of the pipeline to exhaust; the pipeline filter is blocked or the selection is too fine, and the water permeability is limited. You should choose a suitable filter and Clean the filter regularly; the water pump is small and does not match the system.
3. High pressure failure due to fouling or clogging of the condenser
Its performance is that the pressure difference and temperature difference between the inlet and outlet of the deep circulation chiller become larger, and the upper and lower temperatures of the condenser are very high when you touch the condenser by hand, and the condenser outlet copper pipe is hot. The unit should be backwashed regularly, and chemical cleaning and descaling should be carried out if necessary.
4. The refrigerant mixed with air, nitrogen and other non-condensable gases causes high pressure failure
This situation generally occurs after maintenance, and the vacuum is not applied. It can only be drained, re-evacuated, and recharged with refrigerant.
5. False alarms caused by electrical faults produce high-voltage faults
Because the high-voltage protection relay is damp, poorly contacted or damaged, the unit electronic board is damp or damaged, and the communication failure causes a false alarm. For this kind of false fault, the HP fault indicator on the electronic board is often off or slightly bright, the high-voltage protection relay is manually reset invalid, or disappears automatically, the running current of the compressor is normal, and the suction and discharge pressures are also normal.
6. Too much refrigerant charge causes high pressure failure
This situation generally occurs after maintenance, and it is manifested as high suction and exhaust pressure and balance pressure, and high compressor operating current. It should be vented according to the suction and discharge pressure, balance pressure and operating current under rated conditions until normal.
관련 추천
-
국가 하이테크 기업 인증을 세 번째로 획득했습니다.
47602021년 11월 장쑤성 과학기술부는 '2021 장쑤성 하이테크 기업 기록 홍보 목록'을 발표했고, LNEYA는 심사를 성공적으로 통과했습니다. 이것은 회사가 세 번째로 ...
세부 정보 보기 -
2023년 LNEYA 춘절 연휴 안내
2695I have been busy all year, and I am happy to celebrate the new year. The Chinese New Year is coming, and LNEYA is also preparing for the Chinese New Year holiday! Combined with the specific situation of the company, the specific arrangements for ...
세부 정보 보기 -
열유 난방 시스템 설치 및 고장 분석
2313열전달 오일 난방 시스템 장치를 설치할 때 설치 중 일부 결함을 피하기 위해 시스템에주의를 기울여야합니다. 결함이 발생하면 열전달 오일과 관련된 결함을 이해해야합니다.
세부 정보 보기 -
저온 냉각 윤활유 선택 시 고려 사항
2406극저온 냉각기를 사용할 때는 냉각기의 모든 측면에 대해 확실히 알고 싶을 것입니다. 그러나 모든 사람의 주의가 필요한 것 중 하나는 냉장용 윤활유의 종류가 많은 영향을 미치기 때문에 선택된다는 것입니다.
세부 정보 보기
工業冷水機製造商 LNEYA Taiwan