저온 순환 장치의 프로스팅을 해결하는 방법은 무엇입니까?
The failure of the low temperature circulation device frosting is mainly because the compressor return air temperature is too low, which may be that the throttle valve liquid refrigerant supply is in a normal state in the low temperature circulation device, but the low temperature circulation device evaporator cannot normally absorb the heat supply refrigerant expansion; It may also be because the evaporator is in a normal working state but the refrigerant supply throttle valve is too large, causing the low pressure to cause the compressor return air temperature to be too low.
After a little frosting, because the heat insulation layer on the surface of the evaporator has low heat, the refrigerant will transfer to other areas after expansion, causing frosting in the evaporator of the low-temperature circulation device, which will cause the low-temperature circulation device to evaporate. The insulation layer appears to expand to the compressor return pipe causing the compressor to return to air and frost. When the low temperature circulation device has less refrigerant, it is found that the low pressure of the evaporator causes the evaporation temperature to be low, so that the expansion point of the frost layer on the surface of the evaporator is transferred to the compressor return air to cause frosting of the compressor.
In the face of such a phenomenon of frosting of the compressor, Wuxi Yuze suggested that if the system has a heat exchanger bypass valve, then it is only necessary to adjust the hot gas bypass valve. The low temperature circulation device is running this process.
Open the rear end cover of the hot gas bypass valve of the low temperature circulation device, and then use the hex wrench of the toolbox to turn the adjusting nut clockwise. The adjustment process of the defrosting process should not be too fast. Generally, the half cycle is suspended. Let the low temperature circulation device refrigeration system run for a period of time and then look at the frost condition before deciding whether to continue to adjust. Wait for the low-temperature cycle device to run stably, and then tighten the end cap after the compressor frosting disappears. The defrosting process of the low-temperature cycle device can be solved!
For models below 15 cubic meters, since there is no hot gas bypass valve, if the frosting phenomenon is serious, the take-off pressure of the pressure switch of the condensing fan can be appropriately adjusted. specific method:
First find the pressure switch, remove the adjustment nut of the pressure switch to fix the small piece, then use a Phillips screwdriver to rotate clockwise, the whole adjustment also needs to be carried out slowly, adjust the half turn to see the situation and then decide whether it needs adjustment.
The low-temperature circulation device needs to pay attention when performing defrosting. When the model size of the equipment is very different, pay attention to the difference in details when repairing.
관련 추천
-
방폭형 극저온 냉장 장치 지침
1888방폭형 극저온 냉동 장치는 많은 산업 분야에서 사용됩니다. 사용자가 사용할 때 부적절한 작동을 방지하고보다 효율적인 작동을 위해 해당 사용 지침을 이해해야합니다. 에너지 소비량은 ...
세부 정보 보기 -
냉각수 순환기의 모드가 주로 물 순환인 이유는 무엇인가요?
1719냉각수 순환기는 물을 냉각에 사용하는 방법입니다. 주변 온도가 상승함에 따라 많은 회사에서 순환수 사용이 증가하고 있음을 발견했습니다. 순환수의 보충은 수냉을 목표로합니다 ...
세부 정보 보기 -
저온 냉동고의 누출 감지를 위한 팁
1834Soaking leakage detection The sensibility of soaking leakage detection is higher than bubble test,which is usually applied for small Freon freezer unit. When using it, the equipment prohibited from contacting water in the system should be discharg...
세부 정보 보기 -
반응기의 자동 온도 제어 시스템의 수냉식 냉각기의 비상 사태용
1729In the pharmaceutical and chemical production, the automatic temperature control system of the reactor is widely visible. In order to ensure the safe production of the enterprise, what should users pay attention to when facing unexpected situatio...
세부 정보 보기
工業冷水機製造商 LNEYA Taiwan