Causes and troubleshooting of low-temperature water chillers for photoetching machines
The operator of the low-temperature chiller for lithography machine can have a certain understanding of the related faults and solutions during the operation of the equipment, so as to better use the low-temperature chiller for lithography machine. What is the cause of the failure?
1. Refrigerant leakage:
After the refrigerant leaks in the system, the cooling capacity is insufficient, the suction and discharge pressures are low, the evaporator is not covered with frost or there is a small amount of frost at the corners, if the expansion valve hole is adjusted, the suction pressure still does not change much, and the system is balanced after shutdown The pressure is generally lower than the saturation pressure corresponding to the same environment.
Elimination method: After the refrigerant leaks, do not rush to fill the system with refrigerant, but immediately find the leakage point, and then fill the refrigerant after repair.
2. Too much refrigerant is charged after maintenance:
The amount of refrigerant charged in the refrigeration system after maintenance exceeds the capacity of the system, the refrigerant will occupy a certain volume of the condenser, reduce the heat dissipation area, and reduce the cooling effect. The suction and discharge pressures are generally higher than the normal pressure. Value, the evaporator is not frosting, and the lithography machine uses a low temperature chiller to cool down slowly.
Remedy: According to the operating procedure, the excess refrigerant must be discharged from the high shut-off valve after a few minutes of shutdown. At this time, the residual air in the system can also be discharged.
3. There is air in the refrigeration system:
Air in the refrigeration system will reduce the refrigeration efficiency. The prominent phenomenon is that the suction and discharge pressures increase (but the discharge pressure has not exceeded the rated value), and the temperature from the compressor outlet to the condenser inlet increases significantly. Air, exhaust pressure and exhaust temperature all increase.
Remedy: A few minutes after the shutdown, air can be discharged from the high-pressure shut-off valve several times in succession, and some refrigerant can be properly filled according to the actual situation.
4. The frost on the surface of the evaporator is too thick:
The cold storage evaporator used for a long time should be defrosted regularly. If it is not defrosted, the frost layer on the evaporator pipe will become thicker and thicker. When the entire pipe is wrapped into a transparent ice layer, it will seriously affect the heat transfer and cause the lithography machine The temperature of the low-temperature chiller does not fall within the required range.
Remedy: Stop the machine to defrost, and do not hit the frost layer with iron or wooden sticks to prevent damage to the evaporator pipeline.
5. There is refrigerating oil in the evaporator pipeline:
During the refrigeration cycle, some refrigerating oil remains in the evaporator pipeline. After a long period of use, when there is a large amount of residual oil in the evaporator, it will seriously affect the heat transfer effect and cause poor cooling.
Remedy: Remove the refrigerant oil in the evaporator. Remove the evaporator, blow it out, and then dry it.
After the low-temperature chiller for lithography machine has a liquid hammer failure, if the operator or user cannot solve it in time, please contact the manufacturer to solve it.
to sum up
We must clean up and maintain the equipment in time, so as to enhance the life of the equipment.
관련 추천
-
극저온 냉장고의 크라이오 펌프 설치 지점
2311극저온 냉장고의 건설에서 크라이오 펌프는 필수입니다. 저온 냉동고 제조업체 인 LNEYA는 크라이오 펌프가 설치 될 때 요구 사항에 따라 작동해야한다고 모든 사람에게 알려줍니다. 설치 시설 ...
세부 정보 보기 -
TCU 온도 제어 모델 선택 및 기술 파라미터 설명
2611TCU 온도 제어는 2사이클 단위 단일 유체 온도 제어 시스템이기도 합니다. 모델을 선택할 때 전체 온도 제어 반응에 매우 중요합니다. 적절한 반응 시스템만이 발열 및 흡수에 사용됩니다.
세부 정보 보기 -
What is a laboratory glycol chiller What should I pay attention to
2368The laboratory glycol chiller is a common cooling equipment in the laboratory. It is generally used to achieve the temperature requirement of the cold source. What are the benefits? 1. Why choose a laboratory glycol chiller: The single-machine s...
세부 정보 보기 -
좋은 소식입니다! 우시 관야 LNEYA 냉동이 새로운 이름을 얻었습니다.
4363장쑤성 쑤난 국가 독립 혁신 시범구에서 발표한 '2019년 장쑤성 남부 국가 독립 혁신 시범구 유니콘 및 가젤 기업 평가 결과 발표에 관한 통지'에 따르면, 장쑤성 쑤난 국가 독립 혁신 시범구에서 유니콘 및 가젤 기업에 대한 평가 결과가 발표되었습니다.
세부 정보 보기
工業冷水機製造商 LNEYA Taiwan