온도 충격 테스트 장비의 고온 고장 처리
The whole function of Wuxi Guanya LNEYA thermal shock test chamber is computer controlled. It is a self-developed software with a good operation interface, which makes the operation and monitoring of the user simpler and more intuitive. The maintenance function can keep the running program in your operation. In the current state, the value of this block can be temporarily changed. The time parameter can be set on the screen to make the cooling, heating, and blue transfer switch automatically, according to the set value. The cold box and the hot box are independently controlled, and the box doors are independent of each other, and the use range of the test box is expanded (one box and three uses). The thermal shock effect of the temperature impact test equipment can be fully guaranteed. The test box door is interlocked with the circulating fan and the blue drive to protect the operator’s safety. Once the door is opened, the power of the circulating fan and the blue drive will be automatically cut off.
The cause of the high-voltage failure of the temperature shock test equipment may be that the cooling water flow is insufficient and the rated water flow rate is not reached. The main performance is that the pressure difference between the unit inlet and outlet water becomes smaller (compared with the pressure difference at the beginning of the system operation), and the temperature difference becomes larger. The reason for the lack of water flow is that the system is short of water or air. The solution is to install an exhaust valve at the high point of the pipeline to exhaust; the pipeline filter is blocked or too fine, and the water permeability is limited. A suitable filter should be used. Clean the filter regularly; the pump is small and not compatible with the system.
The temperature impact test equipment condenser is fouled or clogged. Condensed water is generally tap water, it is easy to scale at 30 ° C or above, and because the cooling tower is open, it is directly exposed to the air, dust foreign matter can easily enter the cooling water system, causing the condenser to be blocked and the heat exchange area is small. It is inefficient and affects water flow. The performance is that the pressure difference between the inlet and outlet water of the unit is large, and the temperature difference is large. The temperature above and below the condenser is high, and the copper tube of the condenser is hot. The unit should be backwashed regularly and chemically cleaned and descaled if necessary.
The temperature shock test equipment has too much refrigerant charge. This situation generally occurs after maintenance, which is characterized by high suction and discharge pressure, equilibrium pressure, and high compressor operating current. It should be vented according to the suction and exhaust pressure and the equilibrium pressure and the operating current under rated conditions until normal. The temperature impact test equipment is mixed with non-condensable gases such as air and nitrogen in the refrigerant. This situation usually occurs after maintenance, and the vacuum is not complete. Can only be drained, re-vacuum, refill the refrigerant.
False alarm caused by electrical failure of temperature shock test equipment. Due to the moisture, poor contact or damage of the high voltage protection relay, the unit electronic board is damp or damaged, and the communication failure causes a false alarm. This kind of false fault, often the HP fault indicator on the electronic board is not bright or slightly bright, the manual reset of the high voltage protection relay is invalid, the computer displays “HPRESET”, or it disappears automatically, the compressor running current is normal, and the suction and exhaust pressure is also normal. .
If the high-voltage fault of the temperature shock test equipment occurs, it needs to be solved in time to avoid the big fault caused by the small fault and cannot be used in time.
관련 추천
-
열수력 원자로에 사용되는 냉동 가열 온도 제어 시스템 장비
1754냉동 가열 온도 제어 시스템은 다양한 반응기, 반응기 및 증류 장비에 사용할 수 있습니다. 오늘은 열수 반응기에 적용할 때 주의해야 할 사항을 분석해 보겠습니다. 열전달 매체 ...
세부 정보 보기 -
암모니아 냉동 시스템에서 산업용 냉각기의 배출 작동 단계
2027The rubber hose used to connect the outlet valve joint causes one end to be inserted into the water of the water container. When the ammonia in the mixed gas is cooled into ammonia liquid, the bottom of the air separator will frost. At this time, ...
세부 정보 보기 -
Hybrid car battery test equipment cooling capacity description
1990Due to insufficient insulation thickness of the hybrid vehicle battery test equipment and pipeline or damage to the insulation layer, the loss of cooling capacity is increased, which affects the cooling effect. In the operation of the hybrid vehic...
세부 정보 보기 -
The Application of Industrial Chillers
1747The chiller machine is needed in a lot of industries, basically chemical, medical, pharmaceutical industries are involved, then what industry can Wuxi Lneya chiller meet in the end? It is known that we are one of the top chiller manufacturers. Th...
세부 정보 보기
工業冷水機製造商 LNEYA Taiwan