ISG/TM 모터 테스트 냉각 시스템 고전압 고장 및 처리 조치
ISG/TM 모터 테스트 냉각 시스템은 업계에서 공랭식과 수랭식의 두 가지 유형으로 나뉩니다. 작동 원리는 먼저 기계의 물 탱크에 일정량의 물을 주입한 다음 ISG/TM 모터 테스트 냉각 시스템을 통과시켜 물을 냉각하는 것입니다. 그런 다음 저온 냉각수는 워터 펌프를 통해 냉각될 장비로 보내집니다. 냉각 된 물은 열을 제거한 다음 온도가 상승하여 물 탱크로 돌아와 냉각을 달성합니다....
ISG/TM 모터 테스트 냉각 시스템 고전압 고장 및 처리 조치
(1). The cooling water temperature is too high and the condensation effect is poor. ISG/TM motor test cooling system has high water temperature and poor heat dissipation, which will inevitably lead to high condensing pressure. This phenomenon often occurs in high-temperature seasons. The reason for the high water temperature may be: cooling tower failure, such as the fan is not turned on or even reversed, the water distributor does not turn, it is manifested as the cooling water temperature is very high and rising rapidly; the outside temperature is high, the water path is short, and the amount of water that can be circulated In this case, the cooling water temperature is generally maintained at a relatively high level, which can be solved by increasing the storage tank.
(2) The cooling water flow rate is insufficient, and the rated water flow rate is not reached. The main performance is that the pressure difference between the inlet and outlet water of the unit becomes smaller (compared with the pressure difference at the beginning of the system’s operation), and the temperature difference becomes larger. The reason for the insufficient water flow is the lack of water in the system or the presence of air. The solution is to install an exhaust valve at the height of the pipeline to exhaust; the pipeline filter is blocked or the selection is too fine, and the water permeability is limited. You should choose a suitable filter and Clean the filter regularly; the water pump is small and does not match the system.
(3), the condenser is fouled or blocked. Condensate water generally uses tap water, which is easy to scale, and because the cooling tower is open, it is directly exposed to the air. Dust and foreign matter can easily enter the cooling water system, causing the condenser to be dirty and blocked, the heat exchange area is small, and the efficiency is low. Affect water flow. The performance is that the pressure difference and temperature difference between the inlet and outlet water of the unit become larger, and the upper and lower temperatures of the condenser are very high when the condenser is touched by hand. The unit should be backwashed regularly, and chemical cleaning and descaling should be carried out if necessary.
(4), the refrigerant is overcharged. This situation generally occurs after maintenance, and it is manifested as high suction and exhaust pressure and balance pressure, and high compressor operating current. It should be vented according to the suction and discharge pressure, balance pressure and operating current under rated conditions until normal.
(5), the refrigerant is mixed with non-condensable gases such as air and nitrogen. This situation generally occurs after maintenance, and the vacuum is not at the bottom. It can only be drained, re-evacuated, and recharged with refrigerant.
(6) False alarms caused by electrical faults. Because the high-voltage protection relay is damp, poorly contacted or damaged, the unit electronic board is damp or damaged, and the communication failure causes a false alarm. This kind of false fault, often the HP fault indicator on the electronic board is not bright or slightly bright, the high-voltage protection relay manual reset is invalid, the computer displays “HPRESET”, or disappears automatically, the running current of the compressor is normal, and the suction and discharge pressures are also normal.
관련 추천
-
칩 생산 고온 및 저온 에이징 테스트 챔버의 기능은 무엇인가요?
1977현재 칩 웨이퍼 생산 업계는 전례 없는 도전과 변화에 직면해 있습니다. 기술 외에도 생산량은 항상 업계의 관심사였습니다. 칩의 탄생에는 많은 공정이 필요하고 좋은 칩이 필요하다는 것을 우리 모두 알고 있습니다.
세부 정보 보기 -
알아야 할 수냉식 냉각기의 장점
2158산업용 냉각기는 일반적으로 냉동 유형에 따라 수냉식 및 공냉식으로 나눌 수 있습니다. 수냉식 냉각기의 열교환 매체는 물입니다.LNEYA는 새로운 유형의 온도 제어를 설계하고 개발했습니다 ...
세부 정보 보기 -
How to choose low temperature and high temperature aging test equipment?
2175The refrigeration capacity and temperature range of materials in different industries are different. Generally speaking, the cooling capacity is divided into 80kw, 120kw, 180kw, 240kw, 360kw, and the cooling temperature ranges from -25°C to -5°C. ...
세부 정보 보기 -
화학 산업에서 산업용 냉각기의 디버깅 단계
2023After completing the installation of industrial water chillers in chemical enterprises, certain debugging needs to be carried out in the early stage of operation. Only through careful debugging can we find out whether there are hidden troubles in...
세부 정보 보기
工業冷水機製造商 LNEYA Taiwan