Why is there air in the reactor temperature control system?
The impurity gas in the reactor temperature control system is to increase the condensing pressure of the refrigeration system, thereby increasing the condensing temperature, increasing the exhaust temperature of the compressor, increasing the power consumption, reducing the cooling efficiency, and possibly the exhaust gas temperature is too high. The carbonization of the lubricating oil affects the lubrication effect, and in severe cases, the refrigeration compressor motor is burnt.
The gas generated in the reactor temperature control system may be leaking air. It may be when the refrigerant is filled or lubricated, the outside air is taken into the air, or the temperature of the reactor temperature control system is not tight enough to cause air to enter. Inside the system. In addition, gas is generated due to decomposition of the refrigerant oil, impure refrigerant, and corrosion of the metal material. Of course, Wuxi Guanya uses a fully enclosed circulation system on the reactor temperature control system to prevent this air from entering the reactor temperature control system.
In general, the gas in the reactor temperature control system is expressed in the reactor temperature control system compressor exhaust pressure and exhaust gas temperature rise, the pressure gauge pointer on the condenser (or reservoir) violently swings, the compressor The cylinder hair is hot, the condenser shell is very hot; the surface temperature of the evaporator temperature control system is unevenly frosted. When there is a large amount of gas in the reactor temperature control system, the ambient temperature cannot be lowered due to the decrease of the cooling capacity of the reactor. The machine runs for a long time, and even the high-pressure relay operates to stop the compressor.
If the reactor temperature control system has these gases, the pressure of the refrigeration system can be measured by a pressure gauge to compare with the saturation pressure at that ambient temperature. If the measured pressure is greater than the saturation pressure at ambient temperature, the system contains gas.
If the above-mentioned gases are found in the reactor temperature control system, it is necessary to eliminate these gases in time and solve the faults in time.
관련 추천
-
소형 가스 응축 액화 시스템의 파라미터
2123휘발유를 적재 및 하역하고 차량에 연료를 공급하고 화학 공장에서 고농도 가스를 수집하는 과정에서. 흡착 또는 응축 과정에서 한두 가지 방법 또는 가스에서 오일과 가스를 전환하는 과정에서 ...
세부 정보 보기 -
Brief introduction of explosion-proof curve heating and cooling thermostat
1882The explosion-proof curve heating and cooling thermostat SUNDI series adopts compressor refrigeration and linkage heating technology, an integrated piping system, and a plate heat exchanger. It is suitable for equipment connecting reactors for ref...
세부 정보 보기 -
Temperature conditions of new energy vehicle batteries
1828When automobile manufacturers continue to improve battery life to overcome the driver's mileage anxiety, the energy density of the large batteries installed is also gradually increasing, which means that the temperature monitoring function of the...
세부 정보 보기 -
Liquid Cooled Battery Pack BMS Test Cooling Water Circulator
2321As the temperature gradually increases, the use of the cooling water circulator for the BMS test of the liquid-cooled battery pack also gradually peaks. The rated power of the cooling water circulator for BMS testing of liquid-cooled battery packs...
세부 정보 보기
工業冷水機製造商 LNEYA Taiwan