Multi-stage refrigeration system centrifugal compressor repair instructions
After the centrifugal compressor of the cascade refrigeration system is disassembled, the dimensions of each journal (cooperating with the impeller, bearing, coupling, etc.) are measured with an outer diameter micrometer to calculate the roundness and cylindricity deviation. The value should be Within the allowable range. When the tolerance is large, check if the straightness deviation of the spindle is too large. Place the spindle in the casing or place it on the top of the lathe so that the spindle is in a free state. Use a dial gauge to measure the radial runout of the spindle journal.
The centrifugal compressor of the cascade refrigeration system is divided into 4-8 equal parts, and the rotor is driven according to the direction of rotation of the rotor. The large value of the dial gauge swing is the radial circle runout value. At the same time, the straightness deviation of the main shaft is measured at the appropriate position of the main shaft with two dial gauges, and the radial runout value should be no more than 0.01mm. If the over-standard is too large, the main shaft should be replaced.
Check the surface of the journal of the centrifugal compressor of the cascade refrigeration system for scratches, grooves, scratches, grinding points, etc. If necessary, perform flaw detection. Small defects can be scraped and polished by hand; large defects It can be repaired by surfacing, electroplating, spraying, etc., and then ground and polished. When the flaw detection reveals cracks or serious defects, it is generally not repaired and replaced.
At the same time, the end face runout of the centrifugal compressor impeller of the cascade refrigeration system should be measured, and the value should be within the allowable range. If the value of the end face jump exceeds the allowable range value, when the over-standard is small, the repair is generally not performed. When the value is large, the assembly relationship between the impeller and the main shaft can be adjusted by the method of adding the gasket. The impeller should be dynamically balanced and statically balanced after the overhaul. test.
The parts and fittings of the centrifugal compressor of the cascade refrigeration system have the specified technical standards and requirements for use. In the absence of reliable basis, it is necessary to strictly abide by these standards and never lower the standard.
The cascade refrigeration system should have a fixed maintenance and repair plan, carefully learn the correct understanding and use of equipment requirements by the user, and timely cooperate with the on-site user for regular maintenance.
Related recommendations
-
Advantages of Cold Plate Freezer
1886The freezing method is mainly used when the capacitive liquid crystal touch panel of smartphones and tablet computers has defects in production, such as bubbles, foreign objects, black spots, white spots, misplaced..., and needs to be used for rew...
View details -
High-quality professional equipment helps the laboratory to produce endless results
3162In recent years, China's economy has continued to grow. Under the development opportunity of professional high and low temperature integrated machines, laboratory scientific and technological achievements are also in sustainable development. LNEYA...
View details -
What Are the Features of the Glycol Refrigeration System
2037The difference between the glycol refrigeration system and the general refrigeration system is that the glycol solution is used as refrigerant to run the refrigeration system. The glycol refrigeration system is widely used. It can be used in many ...
View details -
Description of the development of the wafer chip test system
1856With the development of the semiconductor industry, the wafer chip test machine has also made great progress. How much do you know about the development of the wafer chip test machine? The integrated circuit industry has gradually emerged since th...
View details
工業冷水機製造商 LNEYA Taiwan